    Ask Lasest Price
    Brand Name : GENY
    Model Number : YCS-103
    Certification : ISO, CE
    Price : negotiate rates
    Payment Terms : T/T, L/C, D/P, T/T
    Supply Ability : 5 sets / 1 months
    Delivery Time : 6~8weeks
    • Product Details
    • Company Profile

    YCS-103/101 Series High-Precision Harmonic Power Equipment OEM / ODM Services

    YCS-103/101 Series High-Precision Harmonic Power Equipment OEM/ODM Services

    Description:

    YCS—103

    • Constructed from aluminum alloy materials, this device boasts a combination of lightweight properties and robustness, effectively preventing corrosion while ensuring high accuracy and stability in output.
    • Equipped with an optional keyboard, facilitating manual operation as needed.
    • Capable of outputting from the 2nd to the 21st harmonic, with programmable amplitudes and degrees.
    • Easily operable via PC control software suite, streamlining operation processes.
    • Features an RS232 interface, enabling automatic operation and integration with external systems.
    • Incorporates protective measures against overload, short voltage circuits, and open current circuits, ensuring safety and reliability during operation.

    YCS-101

    • High accuracy and high stability source output
    • With RS232 interface for automatic operation
    • With keyboard for manual operation (optional).
    • 2nd – 21st harmonic, output amplitude and degree can be programmed.
    • Aluminum alloy materials, light and strong, prevent corrosion.
    • With the protect function of overload, short voltage circuit and open current circuit.
    • PC control software suit, easy operation and support secondary software development

    Technical Specifications:


    ParameterYCS-103-250YCS-103-600YCS-103-1200YCS-103-2500
    Voltage
    Test Voltage Output (Phase-Neutral)3×(24V – 288V) or customized3×(24V – 288V) or customized3×(24V – 288V) or customized3×(24V – 288V) or customized
    Power of the Voltage Output3×100VA3×250VA3×500VA3×1000VA
    ResolutionBetter than 0.01% of full scale value of rangeBetter than 0.01% of full scale value of rangeBetter than 0.01% of full scale value of rangeBetter than 0.01% of full scale value of range
    Setting AccuracyBetter than 0.05% at the final range valueBetter than 0.05% at the final range valueBetter than 0.05% at the final range valueBetter than 0.05% at the final range value
    StabilityBetter than 0.005%/h (integration time 150 s)Better than 0.005%/h (integration time 150 s)Better than 0.005%/h (integration time 150 s)Better than 0.005%/h (integration time 150 s)
    Load Regulation from 0-max. Load< 0.01%< 0.01%< 0.01%< 0.01%
    Distortion Factor< 0.3% for linear resistance load< 0.3% for linear resistance load< 0.3% for linear resistance load< 0.3% for linear resistance load
    Harmonics (2nd – 21st)Free programmableFree programmableFree programmableFree programmable
    Current
    Test Current Output3×(1mA – 100A)3×(1mA – 100A)3×(1mA – 100A)3×(1mA – 100A)
    Power of the Current Output3×150VA3×350VA3×750VA3×1500VA
    ResolutionBetter than 0.01% of full scale value of rangeBetter than 0.01% of full scale value of rangeBetter than 0.01% of full scale value of rangeBetter than 0.01% of full scale value of range
    Setting AccuracyBetter than 0.05% at the final range valueBetter than 0.05% at the final range valueBetter than 0.05% at the final range valueBetter than 0.05% at the final range value
    StabilityBetter than 0.005%/h (integration time 150 s)Better than 0.005%/h (integration time 150 s)Better than 0.005%/h (integration time 150 s)Better than 0.005%/h (integration time 150 s)
    Load Regulation from 0-max. Load< 0.01%< 0.01%< 0.01%< 0.01%
    Distortion Factor< 0.3% for linear resistance load< 0.3% for linear resistance load< 0.3% for linear resistance load< 0.3% for linear resistance load
    Harmonics (2nd – 21st)Free programmableFree programmableFree programmableFree programmable
    Phase Angle
    Range0 -- 360°0 -- 360°0 -- 360°0 -- 360°
    Resolution0.01°0.01°0.01°0.01°
    Setting Accuracy0.1°0.1°0.1°0.1°
    Frequency
    Range45Hz – 65Hz45Hz – 65Hz45Hz – 65Hz45Hz – 65Hz
    Resolution0.01Hz0.01Hz0.01Hz0.01Hz
    Voltage Supply
    Voltage Supply3×220/380V±10% or customized3×220/380V±10% or customized3×220/380V±10% or customized3×220/380V±10% or customized
    Frequency50/60Hz±2Hz50/60Hz±2Hz50/60Hz±2Hz50/60Hz±2Hz
    Operating Conditions
    Ambient Temperature-10°C -- +40°C-10°C -- +40°C-10°C -- +40°C-10°C -- +40°C
    Relative Humidity35-- 85%35% -- 85%35% -- 85%35% -- 85%
    YCS-101-250YCS-101-600YCS-101-1200YCS-101-2500
    Voltage Source
    Test voltage output (Phase-Neutral)24V – 288V or customized
    Power of the voltage output100VA250VA500VA1000VA
    ResolutionBetter than 0.01% of full scale value of range
    Setting accuracyBetter than 0.05% at the final range value
    StabilityBetter than 0.005%/h (integration time 150 s)
    Load regulation from 0-max. load< 0.01%
    Distortion factor< 0.3% for linear resistance load
    Harmonics2nd – 21st free programmable
    Current Source
    Test current output1mA – 100A
    Power of the current output150VA350VA750VA1500VA
    ResolutionBetter than 0.01% of full scale value of range
    Setting accuracyBetter than 0.05% at the final range value
    StabilityBetter than 0.005%/h (integration time 150 s)
    Load regulation from 0-max. load< 0.01%
    Distortion factor< 0.3% for linear resistance load
    Harmonics2nd – 21st free programmable
    Phase angle
    Range0 -- 360°
    Resolution0.01°
    Setting accuracy0.1°
    Frequency
    Range45Hz – 65Hz
    Resolution0.01Hz
    Voltage Supply220V±10% or 50/60Hz±2Hz or customized
    Ambient temperature-10°C -- +40°C
    Relative humidity35% -- 90%